6AG1226-6BA32-5XB0

6AG1226-6BA32-5XB0

SIPLUS S7-1200 SM 1226 F-DI 16x24VDC na bazie 6ES7226-6BA32-0XB0 z powłoką ochronną, -25…+55 °C, F-DI 16x 24 V DC, PROFIsafe, szerokość 70 mm, do PL e (ISO 13849-1)/SIL3 (IEC 61508).

Kategoria produktu
Signal modules
Producent
SIEMENS
Seria produktów
S7-1200
General information
Product type designationSM 1226, F-DI 16x24 V DC
based on6ES7226-6BA32-0XB0
Supply voltage
Rated value (DC)24 V
permissible range, lower limit (DC)20.4 V
permissible range, upper limit (DC)28.8 V
power supply according to NEC Class 2 requiredNo
Input current
from backplane bus 5 V DC, max.155 mA; Current consumption (SM Bus, 5 V DC): 155 mA
Digital inputs
from load voltage L+ (without load), max.130 mA; 130 mA + 6 mA / input used + any Vs1/Vs2 current used
Power loss
Power loss, typ.7 W
Digital inputs
Number of digital inputs16; 16 (1oo1) or 8 (1oo2); Note: You can individually assign each pair of inputs "a.x" and "b.x" as a single (1oo2)-channel or as 2 separate (1oo1)-channels
Number of simultaneously controllable inputs
horizontal installation
up to 50 °C, max.16; 16 inputs at 55 °C horizontal
vertical installation
up to 40 °C, max.16; 16 inputs at 45 °C vertical
Input voltage
for signal "0"-30 V DC to +5 V DC
for signal "1"15 V DC to 30 V DC
Input current
for signal "0", max. (permissible quiescent current)0.5 mA
for signal "1", typ.5 mA
Input delay (for rated value of input voltage)
for standard inputs
parameterizableYes; 0.8 / 1.6 / 3.2 / 6.4 / 12.8 ms
Cable length
shielded, max.200 m; unshielded with input filter time of 1.6 ms to 12.6 ms (With an input delay of 0.8 ms, shielded cables must be used for the digital inputs and the sensor supply)
unshielded, max.200 m; Shielded with input filter time of 0.8 ms to 12.6 s (With an input delay of 0.8 ms, shielded cables must be used for the digital inputs and the sensor supply)
Interrupts/diagnostics/status information
Diagnostics indication LED
for status of the inputsYes
Degree and class of protection
IP degree of protectionIP20
Standards, approvals, certificates
Highest safety class achievable in safety mode
Performance level according to ISO 13849-11-channel, Category 3, PL d; 2-channel, Category 3 or 4, PL e
SIL acc. to IEC 61508SIL 2 (single-channel), SIL 3 (two-channel)
Probability of failure (for service life of 20 years and repair time of 100 hours)
Low demand mode: PFDavg in accordance with SIL2< 5.00E-04
Low demand mode: PFDavg in accordance with SIL3< 1.00E-05
High demand/continuous mode: PFH in accordance with SIL2< 1.00E-08 1/h
High demand/continuous mode: PFH in accordance with SIL3< 1.00E-10 1/h
Ambient conditions
Free fall
Fall height, max.0.3 m; five times, in product package
Ambient temperature during operation
min.-25 °C; = Tmin
max.55 °C; = Tmax
permissible temperature change5°C to 55°C, 3°C / minute
Ambient temperature during storage/transportation
min.-40 °C
max.70 °C
Air pressure acc. to IEC 60068-2-13
Storage/transport, min.660 hPa
Storage/transport, max.1 140 hPa
Altitude during operation relating to sea level
Installation altitude above sea level, max.5 000 m
Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
Relative humidity
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
Resistance
Coolants and lubricants
Resistant to commercially available coolants and lubricantsYes
Use in stationary industrial systems
to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
Use on ships/at sea
to biologically active substances according to EN 60721-3-6Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request
to chemically active substances according to EN 60721-3-6Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
to mechanically active substances according to EN 60721-3-6Yes; Class 6S3 incl. sand, dust; *
Usage in industrial process technology
Against chemically active substances acc. to EN 60654-4Yes; Class 3 (excluding trichlorethylene)
Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)
Remark
Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!
Conformal coating
Coatings for printed circuit board assemblies acc. to EN 61086Yes; Class 2 for high reliability
Protection against fouling acc. to EN 60664-3Yes; Type 1 protection
Military testing according to MIL-I-46058C, Amendment 7Yes; Discoloration of coating possible during service life
Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830AYes; Conformal coating, Class A
Mechanics/material
Enclosure material (front)
PlasticYes
Dimensions
Width70 mm
Height100 mm
Depth75 mm
Weights
Weight, approx.250 g
Approvals / Certificates