6ED1052-2HB08-0BA2
LOGO! 24RCEO (AC), moduł logiczny, zasilanie/wejścia-wyjścia: 24 V DC/24 V AC/relay, 8 DI/4 DO, bez wyświetlacza, pamięć 400 bloków, modułowo rozszerzalny, Ethernet, zintegrowany serwer WWW, rejestr danych, zdefiniowane przez użytkownika strony WWW, standardowa karta microSD dla LOGO! Soft Comfort V8.4 lub wyższej, możliwość wykonywania starszych projektów połączenie z chmurą, MQTT we wszystkich jednostkach podstawowych LOGO! 8.4.
Kategoria produktu
LOGO!Producent
SIEMENSSeria produktów
LOGO!| Installation type/mounting | |
|---|---|
| Mounting | on 35 mm DIN rail, 4 spacing units wide |
| Supply voltage | |
| Rated value (DC) | |
| 24 V DC | Yes |
| permissible range, lower limit (DC) | 20.4 V |
| permissible range, upper limit (DC) | 28.8 V |
| Rated value (AC) | |
| 24 V AC | Yes |
| Line frequency | |
| permissible range, lower limit | 47 Hz |
| permissible range, upper limit | 63 Hz |
| Time of day | |
| Time switching clocks | |
| Number | 400; Max. 400, function-specific |
| Power reserve | 480 h |
| Digital inputs | |
| Number of digital inputs | 8 |
| Digital outputs | |
| Number of digital outputs | 4; Relays |
| Short-circuit protection | No; external fusing necessary |
| Relay outputs | |
| Switching capacity of contacts | |
| with inductive load, max. | 3 A |
| with resistive load, max. | 10 A |
| EMC | |
| Emission of radio interference acc. to EN 55 011 | |
| Limit class B, for use in residential areas | Yes; Radio interference suppression according to EN55011, Limit Value Class B |
| Standards, approvals, certificates | |
| Siemens Eco Profile (SEP) | Siemens EcoTech |
| CE mark | Yes |
| CSA approval | Yes; covered by UL cert |
| UL approval | Yes |
| FM approval | Yes |
| developed in accordance with IEC 61131 | Yes |
| according to VDE 0631 | Yes |
| Marine approval | Yes |
| Ecological footprint | |
| environmental product declaration | Yes |
| Global warming potential | |
| global warming potential, (total) [CO2 eq] | 51.5 kg |
| global warming potential, (during production) [CO2 eq] | 9.64 kg |
| global warming potential, (during operation) [CO2 eq] | 42.1 kg |
| global warming potential, (after end of life cycle) [CO2 eq] | -0.364 kg |
| Ambient conditions | |
| Ambient temperature during operation | |
| min. | -20 °C; No condensation |
| max. | 55 °C |
| Ambient temperature during storage/transportation | |
| min. | -40 °C |
| max. | 70 °C |
| Altitude during operation relating to sea level | |
| Ambient air temperature-barometric pressure-altitude | Tmin ... Tmax at 1 080 hPa ... 795 hPa (-1 000 m ... +2 000 m) |
| Dimensions | |
| Width | 71.5 mm; 4 modular widths (MW) |
| Height | 90 mm |
| Depth | 58 mm |
| Approvals / Certificates | |