6ES7513-1AL02-0AB0

6ES7513-1AL02-0AB0

SIMATIC S7-1500, CPU 1513-1 PN, centrální procesorová jednotka s pracovní pamětí 300 KB pro program a 1.5 MB pro data, 1. rozhraní: PROFINET IRT se 2portovým switchem, bitový výkon 40 ns, je nutná paměťová karta SIMATIC.

Kategorie produktu
CPU
Výrobce
SIEMENS
Produktová řada
S7-1500
General information
Product type designationCPU 1513-1 PN
HW functional statusFS03
Firmware versionV2.9
Product function
I&M dataYes; I&M0 to I&M3
Isochronous modeYes; Distributed and central; with minimum OB 6x cycle of 500 µs (distributed) and 1 ms (central)
Engineering with
STEP 7 TIA Portal configurable/integrated from versionV17 (FW V2.9) / V15 (FW V2.5) or higher; with older TIA Portal versions configurable as 6ES7513-1AL01-0AB0
Configuration control
via datasetYes
Display
Screen diagonal [cm]3.45 cm
Control elements
Number of keys8
Mode buttons2
Supply voltage
Rated value (DC)24 V
permissible range, lower limit (DC)19.2 V
permissible range, upper limit (DC)28.8 V
Reverse polarity protectionYes
Mains buffering
Mains/voltage failure stored energy time5 ms
Repeat rate, min.1/s
Input current
Current consumption (rated value)0.7 A
Current consumption, max.0.95 A
Inrush current, max.1.9 A; Rated value
I²t0.02 A²·s
Power
Infeed power to the backplane bus10 W
Power consumption from the backplane bus (balanced)5.5 W
Power loss
Power loss, typ.5.7 W
Storage
Number of slots for SIMATIC memory card1
SIMATIC memory card requiredYes
Work memory
integrated (for program)300 kbyte
integrated (for data)1.5 Mbyte
Load memory
Plug-in (SIMATIC Memory Card), max.32 Gbyte
Backup
maintenance-freeYes
CPU processing times
for bit operations, typ.40 ns
for word operations, typ.48 ns
for fixed point arithmetic, typ.64 ns
for floating point arithmetic, typ.256 ns
CPU-blocks
Number of elements (total)4 000; Blocks (OB, FB, FC, DB) and UDTs
DB
Number range1 ... 60 999; subdivided into: number range that can be used by the user: 1 ... 59 999, and number range of DBs created via SFC 86: 60 000 ... 60 999
Size, max.1.5 Mbyte; For DBs with absolute addressing, the max. size is 64 KB
FB
Number range0 ... 65 535
Size, max.300 kbyte
FC
Number range0 ... 65 535
Size, max.300 kbyte
OB
Size, max.300 kbyte
Number of free cycle OBs100
Number of time alarm OBs20
Number of delay alarm OBs20
Number of cyclic interrupt OBs20; With minimum OB 3x cycle of 500 µs
Number of process alarm OBs50
Number of DPV1 alarm OBs3
Number of isochronous mode OBs2
Number of technology synchronous alarm OBs2
Number of startup OBs100
Number of asynchronous error OBs4
Number of synchronous error OBs2
Number of diagnostic alarm OBs1
Nesting depth
per priority class24
Counters, timers and their retentivity
S7 counter
Number2 048
Retentivity
adjustableYes
IEC counter
NumberAny (only limited by the main memory)
Retentivity
adjustableYes
S7 timer
Number2 048
Retentivity
adjustableYes
IEC timer
NumberAny (only limited by the main memory)
Retentivity
can be setYes
Data areas and their retentivity
Retentive data area (incl. timers, counters, flags), max.128 kbyte; In total; available retentive memory for bit memories, timers, counters, DBs, and technology data (axes): 88 KB
Extended retentive data area (incl. timers, counters, flags), max.1.5 Mbyte; When using PS 6 0W 24/48/60 V DC HF
Flag
Size, max.16 kbyte
Number of clock memories8; 8 clock memory bit, grouped into one clock memory byte
Data blocks
Retentivity adjustableYes
Retentivity presetNo
Local data
per priority class, max.64 kbyte; max. 16 KB per block
Address area
Number of IO modules2 048; max. number of modules / submodules
I/O address area
Inputs32 kbyte; All inputs are in the process image
Outputs32 kbyte; All outputs are in the process image
per integrated IO subsystem
Inputs (volume)8 kbyte
Outputs (volume)8 kbyte
per CM/CP
Inputs (volume)8 kbyte
Outputs (volume)8 kbyte
Subprocess images
Number of subprocess images, max.32
Hardware configuration
Number of distributed IO systems32; A distributed I/O system is characterized not only by the integration of distributed I/O via PROFINET or PROFIBUS communication modules, but also by the connection of I/O via AS-i master modules or links (e.g. IE/PB-Link)
Number of DP masters
Via CM6; A maximum of 6 CMs (PROFINET + PROFIBUS) can be inserted in total
Number of IO Controllers
Integrated1
via CM6; A maximum of 6 CMs (PROFINET + PROFIBUS) can be inserted in total
Rack
Modules per rack, max.32; CPU + 31 modules
Number of lines, max.1
PtP CM
Number of PtP CMsthe number of connectable PtP CMs is only limited by the number of available slots
Time of day
Clock
TypeHardware clock
Backup time6 wk; At 40 °C ambient temperature, typically
Deviation per day, max.10 s; Typ.: 2 s
Operating hours counter
Number16
Clock synchronization
supportedYes
in AS, masterYes
in AS, deviceYes
on Ethernet via NTPYes
Interfaces
Number of PROFINET interfaces1
1. Interface
Interface types
RJ 45 (Ethernet)Yes; X1
Number of ports2
integrated switchYes
Protocols
IP protocolYes; IPv4
PROFINET IO ControllerYes
PROFINET IO deviceYes
SIMATIC communicationYes
Open IE communicationYes; Optionally also encrypted
Web serverYes
Media redundancyYes
PROFINET IO Controller
Services
PG/OP communicationYes
Isochronous modeYes
Direct data exchangeYes; Requirement: IRT and isochronous mode (MRPD optional)
IRTYes
PROFIenergyYes; per user program
Prioritized startupYes; Max. 32 PROFINET devices
Number of connectable IO Devices, max.128; In total, up to 512 distributed I/O devices can be connected via AS-i, PROFIBUS or PROFINET
Of which IO devices with IRT, max.64
Number of connectable IO Devices for RT, max.128
of which in line, max.128
Number of IO Devices that can be simultaneously activated/deactivated, max.8; in total across all interfaces
Number of IO Devices per tool, max.8
Updating timesThe minimum value of the update time also depends on communication share set for PROFINET IO, on the number of IO devices, and on the quantity of configured user data
Update time for IRT
for send cycle of 250 µs250 μs to 4 ms; Note: In the case of IRT with isochronous mode, the minimum update time of 500 µs of the isochronous OB is decisive
for send cycle of 500 µs500 µs to 8 ms
for send cycle of 1 ms1 ms to 16 ms
for send cycle of 2 ms2 ms to 32 ms
for send cycle of 4 ms4 ms to 64 ms
With IRT and parameterization of "odd" send cyclesUpdate time = set "odd" send clock (any multiple of 125 µs: 375 µs, 625 µs ... 3 875 µs)
Update time for RT
for send cycle of 250 µs250 µs to 128 ms
for send cycle of 500 µs500 µs to 256 ms
for send cycle of 1 ms1 ms to 512 ms
for send cycle of 2 ms2 ms to 512 ms
for send cycle of 4 ms4 ms to 512 ms
PROFINET IO Device
Services
PG/OP communicationYes
Isochronous modeNo
IRTYes
PROFIenergyYes; per user program
Shared deviceYes
Number of IO Controllers with shared device, max.4
activation/deactivation of I-devicesYes; per user program
Asset management recordYes; per user program
Interface types
RJ 45 (Ethernet)
100 MbpsYes
AutonegotiationYes
AutocrossingYes
Industrial Ethernet status LEDYes
Protocols
PROFIsafeNo
Number of connections
Number of connections, max.128; via integrated interfaces of the CPU and connected CPs / CMs
Number of connections reserved for ES/HMI/web10
Number of connections via integrated interfaces88
Number of S7 routing paths16
Redundancy mode
H-Sync forwardingYes
Media redundancy
Media redundancyonly via 1st interface (X1)
MRPYes; MRP Automanager according to IEC 62439-2 Edition 2.0, MRP Manager; MRP Client
MRP interconnection, supportedYes; as MRP ring node according to IEC 62439-2 Edition 3.0
MRPDYes; Requirement: IRT
Switchover time on line break, typ.200 ms; For MRP, bumpless for MRPD
Number of stations in the ring, max.50
SIMATIC communication
PG/OP communicationYes; encryption with TLS V1.3 pre-selected
S7 routingYes
S7 communication, as serverYes
S7 communication, as clientYes
User data per job, max.See online help (S7 communication, user data size)
Open IE communication
TCP/IPYes
Data length, max.64 kbyte
several passive connections per port, supportedYes
ISO-on-TCP (RFC1006)Yes
Data length, max.64 kbyte
UDPYes
Data length, max.2 kbyte; 1 472 bytes for UDP broadcast
UDP multicastYes; Max. 5 multicast circuits
DHCPYes
DNSYes
SNMPYes
DCPYes
LLDPYes
EncryptionYes; Optional
Web server
HTTPYes; Standard and user pages
HTTPSYes; Standard and user pages
OPC UA
Runtime license requiredYes; "Small" license required
OPC UA ClientYes
Application authenticationYes
Security policiesAvailable security policies: None, Basic128Rsa15, Basic256Rsa15, Basic256Sha256
User authentication"anonymous" or by user name & password
Number of connections, max.4
Number of nodes of the client interfaces, recommended max.1 000
Number of elements for one call of OPC_UA_NodeGetHandleList/OPC_UA_ReadList/OPC_UA_WriteList, max.300
Number of elements for one call of OPC_UA_NameSpaceGetIndexList, max.20
Number of elements for one call of OPC_UA_MethodGetHandleList, max.100
Number of simultaneous calls of the client instructions for session management, per connection, max.1
Number of simultaneous calls of the client instructions for data access, per connection, max.5
Number of registerable nodes, max.5 000
Number of registerable method calls of OPC_UA_MethodCall, max.100
Number of inputs/outputs when calling OPC_UA_MethodCall, max.20
OPC UA ServerYes; Data access (read, write, subscribe), method call, custom address space
Application authenticationYes
Security policiesAvailable security policies: None, Basic128Rsa15, Basic256Rsa15, Basic256Sha256
User authentication"anonymous" or by user name & password
GDS support (certificate management)Yes
Number of sessions, max.32
Number of accessible variables, max.50 000
Number of registerable nodes, max.10 000
Number of subscriptions per session, max.20
Sampling interval, min.100 ms
Publishing interval, min.500 ms
Number of server methods, max.20
Number of inputs/outputs per server method, max.20
Number of monitored items, recommended max.1 000; for 1 s sampling interval and 1 s send interval
Number of server interfaces, max.10 of each "Server interfaces" / "Companion specification" type and 20 of the type "Reference namespace"
Number of nodes for user-defined server interfaces, max.1 000
Alarms and ConditionsYes
Number of program alarms100
Number of alarms for system diagnostics50
Further protocols
MODBUSYes; MODBUS TCP
Isochronous mode
EquidistanceYes
S7 message functions
Number of login stations for message functions, max.32
Program alarmsYes
Number of configurable program messages, max.5 000; Program messages are generated by the "Program_Alarm" block, ProDiag or GRAPH
Number of loadable program messages in RUN, max.2 500
Number of simultaneously active program alarms
Number of program alarms600
Number of alarms for system diagnostics100
Number of alarms for motion technology objects80
Test commissioning functions
Joint commission (Team Engineering)Yes; Parallel online access possible for up to 5 engineering systems
Status blockYes; Up to 8 simultaneously (in total across all ES clients)
Single stepNo
Number of breakpoints8
Status/control
Status/control variableYes
VariablesInputs/outputs, memory bits, DBs, distributed I/Os, timers, counters
Number of variables, max.
of which status variables, max.200; per job
of which control variables, max.200; per job
Forcing
ForcingYes
Forcing, variablesPeripheral inputs/outputs
Number of variables, max.200
Diagnostic buffer
presentYes
Number of entries, max.1 000
of which powerfail-proof500
Traces
Number of configurable Traces4; Up to 512 KB of data per trace are possible
Interrupts/diagnostics/status information
Diagnostics indication LED
RUN/STOP LEDYes
ERROR LEDYes
MAINT LEDYes
STOP ACTIVE LEDYes
Connection display LINK TX/RXYes
Supported technology objects
Motion ControlYes; Note: The number of technology objects affects the cycle time of the PLC program; selection guide via the TIA Selection Tool
Number of available Motion Control resources for technology objects800
Required Motion Control resources
per speed-controlled axis40
per positioning axis80
per synchronous axis160
per external encoder80
per output cam20
per cam track160
per probe40
Positioning axis
Number of positioning axes at motion control cycle of 4 ms (typical value)5
Number of positioning axes at motion control cycle of 8 ms (typical value)10
Controller
PID_CompactYes; Universal PID controller with integrated optimization
PID_3StepYes; PID controller with integrated optimization for valves
PID-TempYes; PID controller with integrated optimization for temperature
Counting and measuring
High-speed counterYes
Ambient conditions
Ambient temperature during operation
horizontal installation, min.-25 °C; No condensation
horizontal installation, max.60 °C; Display: 50 °C, at an operating temperature of typically 50 °C, the display is switched off
vertical installation, min.-25 °C; No condensation
vertical installation, max.40 °C; Display: 40 °C, at an operating temperature of typically 40 °C, the display is switched off
Ambient temperature during storage/transportation
min.-40 °C
max.70 °C
Altitude during operation relating to sea level
Installation altitude above sea level, max.5 000 m; Restrictions for installation altitudes > 2 000 m, see manual
Configuration
Programming
Programming language
LADYes
FBDYes
STLYes
SCLYes
GRAPHYes
Know-how protection
User program protection/password protectionYes
Copy protectionYes
Block protectionYes
Access protection
protection of confidential configuration dataYes
Password for displayYes
Protection level: Write protectionYes
Protection level: Read/write protectionYes
Protection level: Complete protectionYes
Cycle time monitoring
lower limitadjustable minimum cycle time
upper limitadjustable maximum cycle time
Dimensions
Width35 mm
Height147 mm
Depth129 mm
Weights
Weight, approx.405 g
Approvals / Certificates